How to design the best inverter string access scheme?

Feb 19, 2025

The following string design formula is proposed with reference to the "Design Specifications for Photovoltaic Power Stations (GB 50797-2012)", which meets two conditions at the same time:

  1. The maximum open-circuit voltage of the PV modules after series connection is lower than the maximum access voltage of the inverter;
  2. The MPPT voltage of the PV modules after series connection is within the MPPT voltage range of the inverter.
  3. Formula (1) Parameter meaning: Vdcmax: maximum input voltage of the inverter; the denominator parameter has been introduced above. Formula (2) Parameter meaning: Vmpptmin: minimum MPPT input voltage of the inverter; Vmpptmax: maximum MPPT input voltage of the inverter; t′: maximum high temperature at the installation location of the component; t: maximum low temperature at the installation location of the component; Vpm: peak power voltage of the component; Kv′: temperature coefficient of peak power voltage of the component (generally calculated using the open circuit voltage temperature coefficient Kv).bolog

 